FQXSPCA0023M : Sensor {0} has transitioned to critical from a non-recoverable state.

Sensor {0} has transitioned to critical from a non-recoverable state.

Severity

Critical

Serviceable with log

No

Automatically Notify Support

No

User Action

Complete the following steps until the problem is solved: \n1) Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear of the server), that the air baffle is in place and correctly installed, and that the server cover is installed and completely closed.\n2) Check the ambient temperature. You must be operating within the specifications (see Server Features and specifications for more information).\n3) Make sure that the heat sink for microprocessor n.\n4) (Trained technician only) Replace microprocessor n. (n=microprocessor number)